MATLAB/Simulink电力系统潮流计算仿真
《MATLAB/Simulink电力系统建模与仿真》中94页中的2机5节点电力系统潮流计算仿真,我参数完全按照书中设置,但调试有问题,Update Load Flow之后,得出发电机的三相电压不对称,数据如注释所示。哪位高手知道为啥?注:
Machine: G2
Nominal: 100 MVA 10.5 kV rms
Bus Type: Swing bus
Uan phase:-40.27°
Uab: 52029 Vrms -10.27°
Ubc: 48895 Vrms 157.70°
Uca: 11025 Vrms -122.71°
Ia: 16777 Arms -9.91°
Ib: 16777 Arms -129.91°
Ic: 16777 Arms 110.09°
P: 1.3046e+009 W
Q: -7.6415e+008 Vars [-7.642 pu]
Pmec: 1.3079e+009 W
Torque: 8.3264e+006 N.m
Vf: 6.067 pu
Machine: G1
Nominal: 100 MVA 10.5 kV rms
Bus Type: P & V generator
Uan phase:-40.45°
Uab: 55176 Vrms -10.45°
Ubc: 50638 Vrms 158.65°
Uca: 11025 Vrms -130.09°
Ia: 17338 Arms -21.32°
Ib: 17338 Arms -141.32°
Ic: 17338 Arms 98.68°
P: 1.5654e+009 W
Q: -5.4297e+008 Vars [-5.43 pu]
Pmec: 1.569e+009 W
Torque: 9.9887e+006 N.m
Vf: 6.7898 pu
Machine: Load3
Nominal: 115 kV rms
Bus Type: P & Q load
Uan phase:-46.14°
Uab: 6.2602e+005 Vrms -16.14°
Ubc: 6.1132e+005 Vrms 161.43°
Uca: 30061 Vrms -136.62°
Ia: 300.16 Arms-102.68°
Ib: 300.16 Arms137.32°
Ic: 300.16 Arms17.32°
P: 1.7944e+008 W
Q: 2.7153e+008 Vars
Machine: Load2
Nominal: 115 kV rms
Bus Type: P & Q load
Uan phase:-41.18°
Uab: 6.0512e+005 Vrms -11.18°
Ubc: 5.7431e+005 Vrms 157.92°
Uca: 1.1609e+005 Vrms -121.95°
Ia: 798.9 Arms-92.72°
Ib: 798.9 Arms147.28°
Ic: 798.9 Arms27.28°
P: 5.2087e+008 W
Q: 6.5561e+008 Vars
Machine: Load1
Nominal: 115 kV rms
Bus Type: P & Q load
Uan phase:-40.94°
Uab: 6.3759e+005 Vrms -10.94°
Ubc: 5.8926e+005 Vrms 158.63°
Uca: 1.2147e+005 Vrms -129.49°
Ia: 433.21 Arms-97.84°
Ib: 433.21 Arms142.16°
Ic: 433.21 Arms22.16°
P: 2.6123e+008 W
Q: 4.0079e+008 Vars 如果楼主的问题还没有解决,不妨把模型和参数设置发我邮箱orchis1986@126.com,我会尽快给你回复。 回复 2# chenbo0623
谢谢,已经解决。 回复 2# chenbo0623
知道互联系统潮流计算有什么特别么?和单区域潮流计算相比?请看我的求助。谢谢! 回复 2# chenbo0623
您好,我在搭这个模型,仿真时总是有错误,能否帮我看下,谢谢 看了那,柯布额可以. 再次感谢楼主 这个问题怎么解决的啊 回复 4# MAGICALMT
网络结构突然变化,本来两边平衡机各自平衡系统的,突然结构的改变可能引起大范围的潮流转移。楼主可以自己拼几个系统试试 怎么解决的,我也是这个问题
页:
[1]
2