例如这些结果是什么意思?PWRFLO case: EMS proj: TEST * * * * DETAILED OUTPUT LISTING * * * * Date: 06-MAR-11
A COMPLETE OUTPUT LISTING OF ALL BUSSES WILL BE GIVEN
bus-1 100.0 98.0KV/0.0 ZONE13556.1PGE 622.2QCOND 0.0PLOAD 0.0QLOAD 0.980PU KV BUS TYPE S
bus-2 100.0 1 13556.1PIN 622.2QIN 0.0000PLOSS246.98QLOSS 100.0/112.9
3556.1PNET 622.2QNET -0.9 SLACK ADJ
bus-10 100.0100.3KV/-37.1 ZONE1 3000.0PLOAD 0.0QLOAD 1.003PU KV BUS TYPE
bus-9 100.0 1 -3000.0PIN 0.0QIN 0.0005PLOSS 85.02QLOSS 100.0/ 97.5
-3000.0PNET 0.0QNET
bus-2 100.0109.6KV/ -3.9 ZONE1 0.0PLOAD 0.0QLOAD 1.096PU KV BUS TYPE
bus-1 100.0 1 1 -3556.1PIN -375.3QIN 0.0000PLOSS246.98QLOSS 112.9/100.0
bus-4 100.0 1 13556.1 375.3 0.0000 425.79 0.0
0.0PNET 0.0QNET
bus-3 100.0 96.4KV/ -6.9 ZONE11500.0PGE 16.2QCOND 0.0PLOAD 0.0QLOAD 0.964PU KV BUS TYPE Q
bus-4 100.0 1 11500.0PIN 16.2QIN 0.0001PLOSS 99.52QLOSS 100.0/112.9
1500.0PNET 16.2QNET
bus-4 100.0109.0KV/-10.7 ZONE1 0.0PLOAD 0.0QLOAD 1.090PU KV BUS TYPE
bus-2 100.0 1 1 -3556.1PIN 50.5QIN 0.0000PLOSS425.79QLOSS 0.0QC
bus-3 100.0 1 1 -1500.0 83.3 -0.0006 99.52 112.9/100.0
bus-5 100.0 1 11011.2 -26.8 13.0686 -25.18 139.4
bus-5 100.0 2 11011.2 -26.8 13.0686 -25.18 139.4
bus-5 100.0 3 11011.2 -26.8 13.0686 -25.18 139.4
bus-5 100.0 4 11011.2 -26.8 13.0686 -25.18 139.4
bus-5 100.0 5 11011.2 -26.8 13.0686 -25.18 139.4
0.0PNET 0.0QNET
bus-5 100.0108.0KV/-25.0 ZONE1 0.0PLOAD 0.0QLOAD 1.080PU KV BUS TYPE
bus-4 100.0 1 1-998.2PIN 1.6QIN13.0687PLOSS-25.18QLOSS 136.7QC
bus-4 100.0 2 1-998.2 1.6 13.0687 -25.18 136.7
bus-4 100.0 3 1-998.2 1.6 13.0687 -25.18 136.7
bus-4 100.0 4 1-998.2 1.6 13.0687 -25.18 136.7
bus-4 100.0 5 1-998.2 1.6 13.0687 -25.18 136.7
bus-6 100.0 1 1 -1094.0 73.3 0.0007 72.33 110.8/100.0
bus-7 100.0 13000.0 584.0 0.0002 281.42 106.6/100.0
bus-8 100.0 13084.8 346.3 0.0007 283.32 106.0/100.0
1011.7QUSED 1011.7QCAP SCHEDULED
0.0PNET1011.7QNET
bus-6 100.0 97.2KV/-21.2 ZONE11094.0PGE -1.0QCOND 0.0PLOAD 0.0QLOAD 0.972PU KV BUS TYPE Q
bus-5 100.0 1 11094.0PIN -1.0QIN-0.0004PLOSS 72.33QLOSS 100.0/110.8
1094.0PNET -1.0QNET
bus-7 100.0 99.9KV/-30.2 ZONE1 3000.0PLOAD1800.0QLOAD 0.999PU KV BUS TYPE
bus-5 100.0 1 -3000.0PIN -302.6QIN 0.0010PLOSS281.42QLOSS 100.0/106.6
1497.4QUSED 1497.4QCAP SCHEDULED
-3000.0PNET-302.6QNET
bus-8 100.0101.2KV/-30.2 ZONE1 0.0PLOAD 0.0QLOAD 1.012PU KV BUS TYPE
bus-5 100.0 1 -3084.8PIN -63.0QIN-0.0002PLOSS283.32QLOSS 100.0/106.0
bus-9 100.0 1 13084.8 370.4 84.7737 285.40 0.0
307.4QUSED307.4QCAP SCHEDULED
0.0PNET 307.4QNET
bus-9 100.0 97.8KV/-35.4 ZONE1 0.0PLOAD 0.0QLOAD 0.978PU KV BUS TYPE
bus-10 100.0 13000.0PIN 85.0QIN 0.0032PLOSS 85.02QLOSS 97.5/100.0
bus-8 100.0 1 1 -3000.0 -85.0 84.7734 285.40 0.0
0.0PNET 0.0QNET
实在不太懂,还请会bpa的网友教教我怎么看这些信息。 用记事本打开查看,如果要读取的话,编个小程序把需要的数据读出来就可以了 在输出结果选项里面,指定要输出的选项 bus-1 100.0 98.0KV/ 0.0 ZONE 1 3556.1PGE 622.2QCOND 0.0PLOAD 0.0QLOAD 0.980PU KV BUS TYPE S
100是额定电压98是实际电压 属于分区1发出功率是3556.1MW 现在电科院的BPA都是汉化版本的。你这版本也忒老了吧。 看看。谢谢!