负载设置
大家好,附件里是我建的模型,为什么我用万用表测FixedLoad的有功和无功,测出的结果与设置的相差很大,哪位大哥大姐能帮忙解释下。谢谢了。我要建立电网模型,大家认为负载的模型我应选择哪种呢,我想选择FixedLoad ,不知有什么更好的模型吗,望不腻赐教。 电源电压Mag. (AC:L-L,RMS)你设置的是10kV
注意,这里是相对相的电压,即线电压
而负载的额定电压为Rated Load Voltage (RMS L-G),这里是相对地的电压,你也设置的10kV,和电源电压矛盾,按照惯例中压10kV的话,指的是线电压,这是相电压应该是10/sqrt(3)=5.773kV
你把负载的额定电压换成5773 就对了,注意,电能表上的PQ是三相功率,而你负载里设置的每相功率 另外,有没有高人解释下,P=37.42怎么出来的,换成单相功率为12.47
按照Fixload的公式,P=P0*(V/V0)^NP*(1+Kpf*dF)
式中
dP/dV : Voltage index for real power
dP/dF : Frequency index for real power
lz设置的都为零。
再按照后面的解释:If used in a 3-phase, single-line mode, the RLC values of all phases are changed when the voltage of any one of the phases goes through a zero crossing.The load remains in constant impedance form until 10 cycles of the fundamental frequency is passed.The non-linear characteristic is effective within ±20% of the rated RMS voltage and ±DF% of the rated frequency (DF is defined as minimum of 10, 90/KPF and 90/KQF).Outside this range, the load reverts to constant impedance.
如果电压为额定电压的20%之内表现非线性属性,超过这个范围,这个负载变为常阻抗。那么现在电压为额定电压的1/sqrt(3)=57%,若按照常阻抗来算的话功率应该和电压平方成正比,当电压减小根号3倍,功率应减小3倍???? 楼上的解释很正确,注意参数的对应。
此模型在10个周波内为恒阻抗模型,根据你填入的相电压和功率计算支路阻抗,而实际功率根据施加的电压而定。
10周波后,转入设定的控制进行调整,但以20%为限,超过20%后即锁定为边界电压调整到的功率为限的横阻抗模型。
一般恒定阻抗模型可以选 3 phase loads (Resistive, Inductive and Capacitive)
选fixed load 注意参数设置和电压范围。。 别再以附件的形式嘛,可以直接贴图的,看不了 没有流量 没法看啊~ 谢谢楼上帮忙解答 想顺便请假同步发电机连接此负荷,与连接一个固定的阻抗区别在哪里呢