lvyinchenxi 发表于 2012-4-18 15:46:27

saturation得到的结果分析

BEGIN NEW DATA CASE
c input data for supporting routine SATURA
c Excitation test results for 3-phase transformer
c       UBASE=500kV
c       SBASE=1000MVA
c       IBASE=1000/500=2kA
c
c 345678901234567890123456789012345678901234567890123456789012345678901234567890
c      1         2         3         4         5         6         7         8
$ERASE
SATURATION
50.0    500.0   1000         1       0
.7745         .05185
.8667         .05617
.9542         .06879
.9884         .07803
1.0             .07928
1.035         .08580
1.085         .09732
1.139         .11409
1.212         .14277
          9999
$PUNCH
BLANK LINE ENDING SATURATION DATA
BEGIN NEW DATA CASE
BLANK LINE ENDING ALL CASES

这是我的saturation程序,运行的结果很诡异。结果如下:
C<++++++>Cards punched by support routine on18-Apr-1215:40:02<++++++>
C SATURATION
C 50.0    500.0   1000         1       0
C .7745         .05185
C .8667         .05617
C .9542         .06879
C .9884         .07803
C 1.0            .07928
C 1.035         .08580
C 1.085         .09732
C 1.139         .11409
C 1.212         .14277
C         9999
2.19061681E+031.16703502E+02
2.60562582E+031.26426919E+02
2.33093820E+031.54831898E+02
2.39766523E+031.75629205E+02
2.55072595E+031.78442694E+02
2.53518646E+031.93117850E+02
2.64839109E+032.19046960E+02
2.69957888E+032.56792721E+02
2.83378049E+033.21345401E+02
            9999
在得到的电流和磁通的关系中,曲线不合理。这是怎么回事呢,请大家帮忙找找原因。谢谢了

southernfox 发表于 2015-9-13 15:05:50

本帖最后由 southernfox 于 2015-9-13 15:07 编辑

看不出来

austycmo 发表于 2016-1-12 15:26:36

下一个东西太耗分了

lanbinghe 发表于 2016-3-2 11:12:57

楼主很专业,写得很好!

anb925 发表于 2016-3-2 15:25:52


下一个东西太耗分了

lvyang567 发表于 2016-3-3 16:47:14

你觉得哪里不对?我没看出来啥。你说出来我们交流下

lvyang567 发表于 2016-3-3 16:53:24

好吧,是有点诡异

lvyang567 发表于 2016-3-3 17:03:55

你的电压电流曲线没问题吗?

zhw3211083 发表于 2019-4-9 21:18:57

看到这帖子真是高兴!

sdtkwgb 发表于 2019-4-17 09:30:27

是前期输入的电流电压数据有问题吧?