IEEE3、4、5、9等节点标准试验系统数据,哪位好心的朋友有的话给我发到邮箱278154077@qq.com function mpc = case9%CASE9 Power flow data for 9 bus, 3 generator case.
% Please see CASEFORMAT for details on the case file format.
%
% Based on data from Joe H. Chow's book, p. 70.
% MATPOWER
% $Id: case9.m,v 1.11 2010/03/10 18:08:14 ray Exp $
%% MATPOWER Case Format : Version 2
mpc.version = '2';
%%-----Power Flow Data-----%%
%% system MVA base
mpc.baseMVA = 100;
%% bus data
% bus_i type Pd Qd Gs Bs area Vm Va baseKV zone Vmax Vmin
mpc.bus = [
1 3 0 0 0 0 1 1 0 345 1 1.1 0.9;
2 2 0 0 0 0 1 1 0 345 1 1.1 0.9;
3 2 0 0 0 0 1 1 0 345 1 1.1 0.9;
4 1 0 0 0 0 1 1 0 345 1 1.1 0.9;
5 1 90 30 0 0 1 1 0 345 1 1.1 0.9;
6 1 0 0 0 0 1 1 0 345 1 1.1 0.9;
7 1 100 35 0 0 1 1 0 345 1 1.1 0.9;
8 1 0 0 0 0 1 1 0 345 1 1.1 0.9;
9 1 125 50 0 0 1 1 0 345 1 1.1 0.9;
];
%% generator data
% bus Pg Qg Qmax Qmin Vg mBase status Pmax Pmin Pc1 Pc2 Qc1min Qc1max Qc2min Qc2max ramp_agc ramp_10 ramp_30 ramp_q apf
mpc.gen = [
1 0 0 300 -300 1 100 1 250 10 0 0 0 0 0 0 0 0 0 0 0;
2 163 0 300 -300 1 100 1 300 10 0 0 0 0 0 0 0 0 0 0 0;
3 85 0 300 -300 1 100 1 270 10 0 0 0 0 0 0 0 0 0 0 0;
];
%% branch data
% fbus tbus r x b rateA rateB rateC ratio angle status angmin angmax
mpc.branch = [
1 4 0 0.0576 0 250 250 250 0 0 1 -360 360;
4 5 0.017 0.092 0.158 250 250 250 0 0 1 -360 360;
5 6 0.039 0.17 0.358 150 150 150 0 0 1 -360 360;
3 6 0 0.0586 0 300 300 300 0 0 1 -360 360;
6 7 0.0119 0.1008 0.209 150 150 150 0 0 1 -360 360;
7 8 0.0085 0.072 0.149 250 250 250 0 0 1 -360 360;
8 2 0 0.0625 0 250 250 250 0 0 1 -360 360;
8 9 0.032 0.161 0.306 250 250 250 0 0 1 -360 360;
9 4 0.01 0.085 0.176 250 250 250 0 0 1 -360 360;
];
%%-----OPF Data-----%%
%% area data
% area refbus
mpc.areas = [
1 5;
];
%% generator cost data
% 1 startup shutdown n x1 y1 ... xn yn
% 2 startup shutdown n c(n-1) ... c0
mpc.gencost = [
2 1500 0 3 0.11 5 150;
2 2000 0 3 0.085 1.2 600;
2 3000 0 3 0.1225 1 335;
];