yfshajia 发表于 2011-2-22 09:47:17

4回线路溢出错误,kill=1

采用自编译的4回线路模型经行过电压计算,运算时弹出如下错误
请问是ATP不支持4回运算,还是自身模型的问题?
            KILL code number                Overlay number               Nearby statement number
                        1                         13                               8109
KILL = 1.   Storage exceeded for EMTP List Number 8.   See the dimensioned limit in the case-summary statistics below.The problem
is simply too big for the program as currently dimensioned.Yet, do not forget dynamic dimensioning as described in the Oct., 1993,
newsletter.   In this case,editLISTSIZE.DAT to increase table sizes,and then try again.   Of course, such dynamic expansion is
possible only within limits fixed byLISTSIZE.BPA(used by variable-dimensioning program"VARDIM"as ATP is to be linked).
Sometimes the reason for EMTP table overflow is unclear, and Program Maintenance might wish to inspect the contents of the error
interface vectorsLSTATandFLSTAT.    These now follow.   First comesLSTAT,using (12I10) encoding; then comesFLSTAT,
using (8E15.6) encoding:
LSTAT =      1426      6417      7130       652      2139   17825   24955      4278   -9999   -9999      10         4
LSTAT =       133         0      46         8       134         0      8109   -9999      36      42       133         5
FLSTAT =   4.680030E-02   4.680030E-02   1.248008E-01   1.248008E-01   0.000000E+00   0.000000E+00   0.000000E+00   0.000000E+00
FLSTAT =   0.000000E+00   0.000000E+00   0.000000E+00   5.000000E+01   6.000000E+01   0.000000E+00   0.000000E+00   0.000000E+00
FLSTAT =   0.000000E+00   0.000000E+00   0.000000E+00   0.000000E+00   0.000000E+00   0.000000E+00   0.000000E+00   0.000000E+00
Yet maybe the user would like some suggestions as to why the table in question(List Number 8 )has overflowed.   If such further
information is available,it will now follow immediately ....
List 8 stores past history points for distributed-parameter transmission circuits (lines or cables) in modal form.   Each
propagation mode requires storage, and there are as many modes as there are coupled conductors or phases (e.g., a double-circuit
line will normally have 6 modes).Each mode requires TAU / DELTATentries,where TAU is the modal travel time of the line,
DELTAT is the time-step size,and the division involves integer truncation followed by the addition of unity.
In order to effectively trade memory space among the different EMTP tables (EMTP List Sizes), the user must know how many arrays
(columns) there are in each table.The following tabulation shows the effective multiplicities that are associated with each
independent EMTP List Size (those lists whose lengths are under user control by means of the EMTP variable-dimensioning program
"VARDIM").

yfshajia 发表于 2011-2-22 09:49:58

线路参数是4回线路,两回地线~

Mr.Z571 发表于 2016-10-24 20:06:11

楼主,请问你的这个问题解决了吗,我现在也遇到同样的问题