liangfubo333 发表于 2010-11-11 19:10:40

关于linezt设置问题!

linezt默认的线路长度单位是m,我输入了345000m为什么报错?或者我可不可以把单位改成km?在线等

liangfubo333 发表于 2010-11-11 20:26:00

各位大侠帮我看看,linezt设置那里有问题?

liangfubo333 发表于 2010-11-11 20:28:37

回复 2# liangfubo333
电感和电容参数是每米值还是总值?电阻标的准确是每米值!

liangfubo333 发表于 2010-11-13 09:25:56

各位大侠帮帮忙啊

wangdc 发表于 2010-11-13 12:40:20

R/l= Resistance pr. length in
            The lossless part can be described in three ways
            0. Inductance L' in if Xopt=0 or in if Xopt=power frequency
               Capacitance C' in if Copt=0 or in if Copt=power frequency
            1. Modal surge impedance in ; Z=sqrt(L'/C')
               Modal propagation velocity in ; v=1/sqrt(L'*C')
            2. Modal surge impedance in
               Modal propagation time in ; T=sqrt(L'*C')*length   
            Xopt. and Copt. are set in menu: ATP|Settings/Simulation.
            The user can choose conductance modeling G=0 (the usual case) and G=R*C/L (distortionless)
      length= length of line in
帮助里面的,说的够清楚了吧
Xopt在setting里面设置,如果用的是atpdraw的话

lanboni2010 发表于 2016-5-12 20:32:04

谢谢!::handshake::

bani 发表于 2024-11-12 11:51:19

谢谢楼主的问题